OMYCH25-AC Type 1 AC Surge Protective Device
OMYCH25-AC is a Type 1 AC surge protective device series. Compare the Uc voltage versions and the applicable discharge ratings before specifying a device for the project.
Electrical Specifications by Voltage Version
| Parameter | 275Vac | 320Vac | 385Vac | 440Vac |
|---|---|---|---|---|
| SPD type | Type 1 | Type 1 | Type 1 | Type 1 |
| AC operating voltage Un | 230Vac | 230Vac | 230Vac | 230Vac |
| Maximum continuous operating voltage Uc | 275Vac | 320Vac | 385Vac | 440Vac |
| Nominal discharge current In (8/20 µs) | 25kA | 25kA | 25kA | 25kA |
| Lightning impulse current Iimp (10/350 µs) | 25kA | 25kA | 25kA | 25kA |
| Voltage protection level Up | ≤2.0kV | ≤2.0kV | ≤2.0kV | ≤2.0kV |
| Short-circuit current rating Isccr | 25kA | 25kA | 25kA | 25kA |
| Maximum backup fuse | 315A gG fuse | 315A gG fuse | 315A gG fuse | 315A gG fuse |
Use the column for the selected voltage version. Confirm the supply system, protection configuration and upstream coordination before ordering.
Installation and Mechanical Data
| Main terminal conductors | Screw terminal, 2.5–25mm² |
|---|---|
| Normal / fault indication | Not available |
| Remote contact maximum load | 250V / 0.5A AC; 30V / 3A DC |
| Remote signal conductor cross-section | Maximum 1.5mm² |
| Installation | 35mm DIN rail |
| Operating temperature | -40°C to +85°C |
| Protection level | IP20 |
| Enclosure material | Thermoplastic material, UL94 V-0 |
| Applicable standard reference | IEC/EN 61643-11; GB/T 18802.11 |
The device is rated IP20. IP20 does not provide weatherproof protection. For outdoor panels or exposed locations, confirm a suitable protective enclosure and the installation conditions. Coordinate the backup fuse with the selected device and circuit.
Documents and Order Confirmation
Request the applicable datasheet, dimensional drawing, installation instructions and available certification documents for the exact OOHMAGE model. Confirm the document holder, model coverage, destination market, supply scope and packaging with the quotation.
Before You Request a Quote
Send the AC system voltage, earthing arrangement, required SPD type, pole configuration, discharge ratings, quantity and installation environment.
Compare the OOHMAGE SPD range or use the quotation form below.
Request Quote
Tell us your specifications, quantity, or application scenario and we will reply with a tailored quote.