< img height="1" width="1" src="https://www.facebook.com/tr?id=1523171142290993&ev=PageView&noscript=1"/>

OMYCH25-AC Type 1 AC Surge Protective Device

OMYCH25-AC Type 1 AC surge protection. Uc options: 275 / 320 / 385 / 440Vac.

  • In 25kA
  • IP20; 35mm DIN rail
  • Confirm the voltage version, poles and installation conditions
Outdoor installations require a suitable protective enclosure.

Share to:

OMYCH25-AC Type 1 AC Surge Protective Device

OMYCH25-AC is a Type 1 AC surge protective device series. Compare the Uc voltage versions and the applicable discharge ratings before specifying a device for the project.

Electrical Specifications by Voltage Version

Parameter275Vac320Vac385Vac440Vac
SPD typeType 1Type 1Type 1Type 1
AC operating voltage Un230Vac230Vac230Vac230Vac
Maximum continuous operating voltage Uc275Vac320Vac385Vac440Vac
Nominal discharge current In (8/20 µs)25kA25kA25kA25kA
Lightning impulse current Iimp (10/350 µs)25kA25kA25kA25kA
Voltage protection level Up≤2.0kV≤2.0kV≤2.0kV≤2.0kV
Short-circuit current rating Isccr25kA25kA25kA25kA
Maximum backup fuse315A gG fuse315A gG fuse315A gG fuse315A gG fuse

Use the column for the selected voltage version. Confirm the supply system, protection configuration and upstream coordination before ordering.

Installation and Mechanical Data

Main terminal conductorsScrew terminal, 2.5–25mm²
Normal / fault indicationNot available
Remote contact maximum load250V / 0.5A AC; 30V / 3A DC
Remote signal conductor cross-sectionMaximum 1.5mm²
Installation35mm DIN rail
Operating temperature-40°C to +85°C
Protection levelIP20
Enclosure materialThermoplastic material, UL94 V-0
Applicable standard referenceIEC/EN 61643-11; GB/T 18802.11

The device is rated IP20. IP20 does not provide weatherproof protection. For outdoor panels or exposed locations, confirm a suitable protective enclosure and the installation conditions. Coordinate the backup fuse with the selected device and circuit.

Documents and Order Confirmation

Request the applicable datasheet, dimensional drawing, installation instructions and available certification documents for the exact OOHMAGE model. Confirm the document holder, model coverage, destination market, supply scope and packaging with the quotation.

Before You Request a Quote

Send the AC system voltage, earthing arrangement, required SPD type, pole configuration, discharge ratings, quantity and installation environment.

Compare the OOHMAGE SPD range or use the quotation form below.

Request Quote

Tell us your specifications, quantity, or application scenario and we will reply with a tailored quote.

+86-18757092555 Phone info@oohmage.com E-mail Chat on WhatsApp WhatsApp