Beschreibung
OMYN20-AC Type 2+3 surge protective device
OMYN20-AC is a pluggable Type 2+3 AC surge protective device for coordinated protection of sensitive equipment. The series declares In 10 kA and Imax 20 kA under the 8/20 μs waveform, plus an open-circuit test voltage Uoc of 6 kV. Four Uc options cover 275, 320, 385 and 440 Vac.
Use it in a protection design that accounts for the supply, upstream SPDs and equipment requirements. MOV (metal oxide varistor) technology limits transient overvoltages; thermal disconnection, green/red indication and optional remote signaling support inspection and monitoring.
Voltage versions and Type 3 test data
| Parameter | 275 V | 320 V | 385 V | 440 V |
|---|---|---|---|---|
| Maximum continuous operating voltage Uc (Vac) | 275 | 320 | 385 | 440 |
| Voltage protection level Up (kV) | ≤1.2 | ≤1.3 | ≤1,5 | ≤1.6 |
| TOV withstand, 5 s — Ut (Vac) | 335 | 335 | 580 | 580 |
| TOV disconnection, 120 min — Ut (Vac) | 440 | 440 | 770 | 770 |
| Uoc — open-circuit test voltage (kV) | 6 | 6 | 6 | 6 |
Uc is the maximum continuous operating voltage; Up is the voltage protection level. Uoc 6 kV is an open-circuit test-voltage value, not a continuous operating-voltage rating. TOV voltages describe temporary-overvoltage tests and should not be used as the normal supply voltage.
Connection options and installation data
The series lists 1P, 2P, 1P+NPE, 3P, 4P and 3P+NPE configurations. Match the phases, earthing arrangement and protection modes to the panel. Request the corresponding connection diagram and outline drawing to check the available installation space.
| Electrical / mechanical item | Published value |
|---|---|
| SPD classification | Type 2+3 AC |
| Nominal operating voltage Un | 230 Vac |
| Nominal discharge current In (8/20 μs) | 10 kA |
| Maximum discharge current Imax (8/20 μs) | 20 kA |
| Short-circuit current rating Isccr | 25 kA |
| Maximum backup fuse | 32 A gG |
| Power connection | Screw terminals, 2.5–25 mm² |
| Montage | 35 mm DIN rail |
| Status indication | Green / red |
| Remote signaling | Optional |
| Remote contact load | 250 V / 0.5 A AC; 30 V / 3 A DC |
| Remote conductor cross-section | Maximum 1.5 mm² |
| Betriebstemperatur | −40°C to +85°C |
| Ingress protection | IP20 |
| Gehäusematerial | Thermoplastic, UL94 V-0 |
| Standard references | IEC/EN 61643-11; GB/T 18802.11 |
The 32 A gG figure is the maximum backup-fuse specification. Coordinate upstream protection with the selected SPD, available fault current and circuit design. Install the IP20 device inside a suitable panel or enclosure; outdoor suitability depends on the complete assembly and its installation conditions.
Compare the N-series AC options
For a Type 2 requirement, compare OMYN40-AC, In 20 kA / Imax 40 kA und OMYN60-AC, In 30 kA / Imax 60 kA. Select the required test class first, then compare voltage-specific Up, connection arrangements and installation details. A larger discharge-current rating alone does not replace a required test class.
Verwenden Sie die SPD type and rating selection guide for the wider selection process, or return to the OOHMAGE AC and DC SPD range.
Request a panel-specific quotation
Send OMYN20-AC, the Uc version, connection configuration and quantity through Request Quote. Add the system voltage, earthing arrangement, equipment application and any upstream SPD details. Specify whether remote status monitoring is required.
Request the matching datasheet, Type 2+3 test information, dimensions, wiring diagram and available model-specific certification documents. Confirm destination market, packing quantity, carton details, labeling and delivery requirements with the quotation.
Common selection questions
What does the 6 kV value mean?
The published Uoc is the open-circuit test voltage for this Type 2+3 series. Use the Uc column to select the continuous AC voltage version; do not use Uoc as a supply-voltage rating.
Is OMYN20-AC a Type 1 SPD?
This series is listed as Type 2+3. Its 10/20 kA figures are 8/20 μs discharge ratings and do not establish a 10/350 μs Type 1 lightning impulse-current rating.
Can this AC model be used on a solar DC circuit?
Choose a dedicated DC/PV SPD for the DC circuit. The 275–440 Vac options on this page are AC ratings, rather than PV DC voltage ratings.
How do local indication and remote signaling differ?
The green/red indicator supports inspection at the panel. Optional remote signaling provides status information to a monitoring system. Specify the contact option and check its load rating and wiring diagram before connection.
Angebot anfordern