< img height="1" width="1" src="https://www.facebook.com/tr?id=1523171142290993&ev=PageView&noscript=1"/>

OMR2-D Tripping Class 10 Adjustable Current Thermal Overload Relay

  1. Wide Application Range:
  2. Advanced Mechanism:
  3. Main Circuit Characteristics:
  4. Auxiliary Circuit Features:
  5. Compliance and Safety:
    • IEC 60947-5 Standard: Complies with international safety standards, ensuring reliable and safe operation.
    • Phase Break Protection: Effectively protects against phase break situations, preventing motor damage.

Share to:

Product Description

The OMR2-D Thermal Overload Relay series is designed to protect electric motors in circuits operating at 50Hz or 60Hz with a rated insulation voltage of 660V and a rated current range of 0.1-93A. These relays effectively prevent phase break and motor overload situations. Featuring advanced mechanisms and temperature compensation, they can be easily plugged into OMC-D or OMC1-D series AC contactors. These relays comply with the IEC 60947-5 standard, making them some of the most advanced thermal relays available.

Features

  1. Wide Application Range:
    • Frequency Compatibility: Suitable for circuits operating at both 50Hz and 60Hz.
    • Current Range: Designed for protecting motors with a rated current range from 0.1A to 93A.
  2. Advanced Mechanism:
    • Temperature Compensation: Ensures consistent performance even under varying temperature conditions.
    • Plug-in Design: Can be easily integrated with OMC-D or OMC1-D series AC contactors for seamless installation.
  3. Main Circuit Characteristics:
    • Rated Insulation Voltage: 660V, ensuring robust insulation and safety.
    • Rated Working Current: Options available for 25A, 36A, and 93A, providing flexibility for different applications.
    • Regulator Seal: Adjustable settings for rated current to suit specific motor protection needs.
  4. Auxiliary Circuit Features:
    • N/O and N/C Contacts: Includes one pair of Normally Open (N/O) and Normally Closed (N/C) contacts with electric insulation.
    • Rated Insulation Voltage: 500V for the auxiliary circuit.
    • Frequency: Operates effectively at 50-60Hz.
  5. Compliance and Safety:
    • IEC 60947-5 Standard: Complies with international safety standards, ensuring reliable and safe operation.
    • Phase Break Protection: Effectively protects against phase break situations, preventing motor damage.

Specification

ModelRated working currentThermal component
Rated current Regular or scale of
(A) rated current(A)
OMR2-D1325A13010.16 0.10-0.16
13020.25 0.16-0.25
13030.40 0.25-0.40
13040.63 0.40-0.63
13051.0 0.63-1.0
13061.6 1.0-1.6
13072.5 1.6-2.5
13084.0 2.5-4.0
13106.0 4.0-6.0
13128.0 5.5-8.0
131410.0 7.0-10.0
131613.0 9.0-13.0
132118.0 12.0-18.0
132225.0 17.0-25.0
OMR2-D2336AOMR2-D 235332 23.0-32.0
235536 28.0-36.0
OMR2-D3393AOMR2-D 335332 23.0-32.0
335540 30.0-40.0
335750 37.0-50.0
335965 48.0-65.0
336170 55.0-70.0
336380 63.0-80.0
336593 80.0-93.0