Alçak gerilim sistemleri için AC ve DC SPD serisi

AC & DC Surge Protective Device Manufacturer

AC and DC surge protective devices for panel builders, distributors and solar PV projects. Compare Type 1, Type 1+2 and Type 2 series, check the model ratings, then request technical documents and a quotation.

Choose your SPD type ↓   Compare model ratings ↓

AC ve DC Parafudr ve Aşırı Gerilim Koruma Cihazı Serileri

Compare SPD Ratings by Model

Compare voltage options and current ratings, then open a model for the full specifications.

Six SPD series at a glance
ModelSPD typeVoltage options · UcSurge current ratings
OMYCH25-AC →Tip 1275 / 320 / 385 / 440Vac
Iimp25 kA
İçinde25 kA
OMDH7-AC →Tip 1+2275 / 320 / 385 / 440Vac
Iimp7 / 7 / 7 / 6.25kA
In / Imax20 / 50kA
OMDN40-AC →Tip 2275 / 320 / 385 / 440Vac
In / Imax20 / 40kA
OMDN60-AC →Tip 2275 / 320 / 385 / 440Vac
In / Imax30 / 60kA
OMYCN120-AC →Tip 2275 / 320 / 385 / 440Vac
In / Imax60 / 120kA
OMDH9-DC →Tip 1+2600 / 800 / 1000 / 1200 / 1500Vdc
Iimp12.5 / 12.5 / 9 / 6.25 / 6.25kA
In / Imax20 / 50kA

Iimp: 10/350µs. In / Imax: 8/20µs. Voltage-dependent Iimp values follow the Uc order shown.

Explore SPD Models

SPD supply-chain laboratory with impulse-current, thermal-stability and voltage testing equipment
Supply-chain impulse-current, thermal-stability and voltage testing

Model Support & Quotations

Send AC/DC, voltage and quantity. Add your model number or panel specification if you have one.

  • Model and voltage selection
  • Datasheets, dimensions and wiring
  • Available model test documents
Get a Quote →

SPD Selection FAQs

What is the difference between Type 1, Type 2 and Type 1+2?

Type 1 devices are specified for lightning-current duty and declare an Iimp rating using a 10/350µs waveform. Type 2 devices limit surge overvoltages with 8/20µs current ratings. Type 1+2 combines both test classes. Select the type required by the installation design; a larger Type 2 Imax does not replace a Type 1 requirement.

Which ratings should I compare before choosing an SPD?

Compare the same supply type and test conditions. Check Uc (maximum continuous operating voltage), Up (voltage protection level), the declared surge-current ratings, protection modes and poles. Also check prospective short-circuit current, backup protection and installation requirements. The table above is a shortlist; model pages contain the voltage-specific data.

Which OOHMAGE AC SPD series should I compare?

Start with OMDN40-AC for In 20kA / Imax 40kA, OMDN60-AC for 30/60kA, or OMYCN120-AC for 60/120kA Type 2 options. For a Type 1 specification, compare OMYCH25-AC. For combined Type 1+2, compare OMDH7-AC. Match the chosen voltage version and protection level to your specification.

How do I choose a DC SPD for a solar PV project?

Use the DC/PV model data rather than an AC voltage marking. OMDH9-DC Type 1+2 has 600, 800, 1000, 1200 and 1500Vdc versions with different Iimp and Up values. Provide the maximum PV system voltage and protection design so the correct version, connection arrangement and backup protection can be reviewed.

Can these DIN-rail SPDs be installed outdoors?

The six series in the comparison table are IP20 devices for installation inside suitable equipment enclosures. For an outdoor panel or PV combiner box, select the enclosure and installation arrangement for the actual environment. Include the exposure conditions in your inquiry.

What should I request with my quotation?

Request the exact model and voltage version, pole configuration, dimensions, datasheet, installation information and available model-specific test or certification documents. Include quantity and destination market, and ask for price, packing and lead time. If you have no model number yet, start with AC/DC, voltage and quantity. Add the earthing arrangement, applicable standard and required delivery date when relevant.