OMYT80-AC compact Type 2 surge protection
OMYT80-AC is a compact, DIN-rail AC surge protective device for distribution panels. Its Type 2 ratings are In 40 kA and Imax 80 kA, measured with an 8/20 μs waveform. Compare the voltage version and connection arrangement alongside the current rating when selecting protection for a residential, commercial or industrial panel.
The pluggable module has thermal disconnection and a green/red status indicator. Optional remote signaling supports panel monitoring. These features make inspection and module replacement easier; the correct SPD arrangement still depends on the supply and protection design.
Voltage versions and protection levels
| Tham số | 275 V | 320 V | 385 V | 440 V |
|---|---|---|---|---|
| Maximum continuous operating voltage Uc (Vac) | 275 | 320 | 385 | 440 |
| Voltage protection level Up (kV) | ≤2.0 | ≤2.2 | ≤2.5 | ≤2.8 |
| TOV withstand, 5 s — Ut (Vac) | 335 | 335 | 500 | 580 |
| TOV disconnection, 120 min — Ut (Vac) | 440 | 440 | 650 | 770 |
Uc is the maximum continuous operating voltage; Up is the voltage protection level. Match both to the electrical system and equipment requirements. The TOV figures describe temporary-overvoltage test conditions, rather than continuous operating voltages.
Choose the connection configuration
The series is offered in 2P, 1P+NPE, 4P and 3P+NPE arrangements, with 275, 320, 385 and 440 Vac Uc options. Specify the number of phases, earthing system and required protection modes so the connection diagram can be matched to your panel. Pole count alone does not identify the full protection arrangement.
Electrical and installation data
| Electrical / mechanical item | Published value |
|---|---|
| SPD classification | Type 2 AC |
| Nominal operating voltage Un | 230 Vac |
| Nominal discharge current In (8/20 μs) | 40 kA |
| Maximum discharge current Imax (8/20 μs) | 80 kA |
| Short-circuit current rating Isccr | 25 kA |
| Maximum backup fuse | 125 A gG |
| Power connection | Screw terminals, 2.5–25 mm² |
| Lắp đặt | 35 mm DIN rail |
| Status indication | Green / red |
| Remote signaling | Tùy chọn |
| Remote contact load | 250 V / 0.5 A AC; 30 V / 3 A DC |
| Remote conductor cross-section | Maximum 1.5 mm² |
| Nhiệt độ hoạt động | −40°C to +85°C |
| Ingress protection | IP20 |
| Chất liệu vỏ | Thermoplastic, UL94 V-0 |
| Standard references | IEC/EN 61643-11; GB/T 18802.11 |
Coordinate the backup protection with the available fault current, selected SPD and circuit design. The published 125 A gG value is a maximum backup-fuse specification, not a requirement to fit that fuse in every installation. Install the IP20 device inside a suitable enclosure; outdoor panels need an enclosure selected for their environment.
Compare models and request a quote
Duyệt qua AC and DC SPD range for other surge-current classes and applications. For another 40/80 kA AC option, compare OMYCN80-AC Type 2 SPD, including its dimensions and connection options. Use the SPD type and rating selection guide when defining a panel specification.
Sử dụng Request Quote and send OMYT80-AC, the Uc version, connection configuration, quantity and destination. Add the earthing arrangement, panel space and any remote-contact requirement. Request the matching outline drawing, wiring diagram, datasheet, packing details and delivery schedule. Model-specific test or certification documents can be reviewed with the quotation.
Selection questions
Is OMYT80-AC a Type 1 or Type 1+2 SPD?
This page covers Type 2 AC devices. The 40/80 kA figures are 8/20 μs discharge ratings and do not establish a Type 1 lightning impulse-current rating. Compare a declared Type 1 or Type 1+2 model when the installation design requires that test class.
Can I use this model on a solar DC circuit?
Choose a dedicated DC/PV SPD for a solar DC circuit. The AC voltage versions on this page are not DC ratings. See the OMDN40-DC Type 2 series for a DC alternative, and select it against the PV system voltage and protection design.
Do I need remote signaling?
The local green/red indicator supports visual inspection. Specify the optional remote contact when a monitoring system needs SPD status information, and check the contact load and connection diagram before wiring.