OMYCH12.5-DC Type 1+2 PV surge protective device
OMYCH12.5-DC is a pluggable Type 1+2 DC surge protective device for solar PV protection designs. The series combines a declared 12.5 kA lightning impulse-current rating under the 10/350 μs waveform with In 20 kA and Imax 50 kA ratings under 8/20 μs. Five Ucpv versions cover 600 to 1500 Vdc.
Use the voltage-specific data below when specifying a PV combiner box, inverter DC input protection or another PV distribution assembly. Select the device together with the system voltage, connection arrangement, insulation requirements and coordinated protection design.
Ratings by DC voltage version
| Parametro | 600 V | 800 V | 1000 V | 1200 V | 1500 V |
|---|---|---|---|---|---|
| Ucpv — maximum continuous operating voltage (Vdc) | 600 | 800 | 1000 | 1200 | 1500 |
| Up — voltage protection level (kV) | ≤2.6 | ≤3.2 | ≤3.8 | ≤4.5 | ≤5.2 |
| In — nominal discharge current (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
| Imax — maximum discharge current (8/20 μs) | 50 kA | 50 kA | 50 kA | 50 kA | 50 kA |
| Iimp — lightning impulse current (10/350 μs) | 12.5 kA | 12.5 kA | 12.5 kA | 12.5 kA | 12.5 kA |
| Itotal — multipole total current (10/350 μs) | 25 kA | 25 kA | 25 kA | 25 kA | 25 kA |
Ucpv is the maximum continuous PV operating voltage. Match it against the maximum system voltage, including the PV design’s voltage conditions. Up is the voltage protection level and changes with the selected version. Iimp and Itotal are separately declared test quantities; do not treat the 25 kA multipole total as a 25 kA Iimp rating for each protection path.
Electrical and mechanical data
| Electrical / installation item | Published value |
|---|---|
| SPD class | Type 1+2 DC |
| Tecnologia | MOV (metal oxide varistor) |
| PV short-circuit current rating Iscpv | 10 kA |
| Response time tA | ≤25 ns |
| Maximum backup fuse listing | 160–200 A gPV; select for the exact configuration |
| Power connection | Screw terminals, 2.5–25 mm² |
| Montaggio | 35 mm DIN rail |
| Protection module | Pluggable, with thermal disconnection |
| Status indication | Green / red |
| Remote signaling | Facoltativo |
| Remote contact load | 250 V / 0.5 A AC; 30 V / 3 A DC |
| Remote conductor cross-section | Maximum 1.5 mm² |
| Temperatura di esercizio | −40°C to +85°C |
| Ingress protection | IP20 |
| Materiale dell'involucro | Thermoplastic, UL94 V-0 |
| PV standard references | IEC/EN 61643-31; GB/T 18802.31 |
The 160–200 A gPV figure is the published maximum backup-fuse listing. Confirm the applicable fuse and upstream coordination for the selected voltage and connection configuration. Install this IP20 DIN-rail device inside a suitable enclosure; outdoor use depends on the complete enclosure and installation arrangement.
Specify the PV connection and documents
- Provide the maximum PV system voltage and required Ucpv version.
- Identify the positive, negative and earth connections, earthing arrangement and required protection modes.
- Check Up, available fault current and upstream protective devices against the panel design.
- Specify local inspection or optional remote status monitoring, and request the matching wiring diagram.
Request the outline drawing, datasheet and available model-specific test or certification documents for the chosen configuration. Confirm the document’s model scope and market requirements with the quotation.
Compare related PV protection options
Compare OMDH9-DC Type 1+2 SPD by voltage-specific Iimp, Up and connection details. For a Type 2 requirement, review OMDN40-DC Type 2 SPD. Select the required test class before comparing kA figures.
See the solar PV surge protection guide for application context, or return to the OOHMAGE SPD range to compare AC and DC series.
Request a project quotation
Utilizzo Request Quote and include OMYCH12.5-DC, the 600 / 800 / 1000 / 1200 / 1500 Vdc version, connection arrangement and quantity. Add the panel or combiner specification, destination market, document requirements and delivery date. Confirm dimensions, remote signaling, packing quantity, labeling and shipping details for the selected configuration.
Common selection questions
Is OMYCH12.5-DC a Type 2-only SPD?
This series is listed as Type 1+2 and declares both 10/350 μs impulse and 8/20 μs discharge ratings. Compare the required protection class and each test waveform rather than treating all kA figures as interchangeable.
Can I choose the version using the inverter’s nominal voltage alone?
Use the maximum PV system voltage and the complete protection design. A nominal operating voltage does not capture every voltage condition used in PV selection. Provide the system specification when requesting the model.
Can the device be mounted outdoors without an enclosure?
The device is IP20. An outdoor PV combiner or panel needs an enclosure and installation arrangement suitable for its exposure conditions. The device’s temperature range does not make it weatherproof.
Are the module indicator and remote contact the same feature?
The green/red indicator provides local status information. Optional remote signaling supports monitoring away from the device; specify the contact option and use the corresponding connection drawing.