OMYT40-AC compact Type 2 surge protection
OMYT40-AC is a compact Type 2 AC surge protective device for low-voltage distribution boards. It provides In 20 kA and Imax 40 kA ratings under the 8/20 μs test waveform. The series is suited to panel specifications calling for this discharge-current class, with voltage and connection options for different AC protection arrangements.
A pluggable protection module, thermal disconnection and green/red indication support inspection and replacement. Remote signaling is optional. For panel builders, distributors and project buyers, the useful comparison is the complete configuration: Uc, Up, protection modes, connection arrangement and available installation space.
Voltage versions and protection levels
| Parameter | 275 V | 320 V | 385 V | 440 V |
|---|---|---|---|---|
| Maximum continuous operating voltage Uc (Vac) | 275 | 320 | 385 | 440 |
| Voltage protection level Up (kV) | ≤1,5 | ≤1.6 | ≤1.8 | ≤2.0 |
| TOV withstand, 5 s — Ut (Vac) | 335 | 335 | 500 | 580 |
| TOV disconnection, 120 min — Ut (Vac) | 440 | 440 | 650 | 770 |
Uc is the maximum continuous operating voltage; Up is the voltage protection level. Match both to the electrical system and equipment requirements. The TOV figures describe temporary-overvoltage test conditions, rather than continuous operating voltages.
Choose the connection configuration
The series is offered in 2P, 1P+NPE, 4P and 3P+NPE arrangements, with 275, 320, 385 and 440 Vac Uc options. Specify the number of phases, earthing system and required protection modes so the connection diagram can be matched to your panel. Pole count alone does not identify the full protection arrangement.
Electrical and installation data
| Electrical / mechanical item | Published value |
|---|---|
| SPD classification | Type 2 AC |
| Nominal operating voltage Un | 230 Vac |
| Nominal discharge current In (8/20 μs) | 20 kA |
| Maximum discharge current Imax (8/20 μs) | 40 kA |
| Short-circuit current rating Isccr | 25 kA |
| Maximum backup fuse | 63 A gG |
| Power connection | Screw terminals, 2.5–25 mm² |
| Pemasangan | 35 mm DIN rail |
| Status indication | Green / red |
| Remote signaling | Opsional |
| Remote contact load | 250 V / 0.5 A AC; 30 V / 3 A DC |
| Remote conductor cross-section | Maximum 1.5 mm² |
| Suhu pengoperasian | −40°C to +85°C |
| Ingress protection | IP20 |
| Bahan penutup | Thermoplastic, UL94 V-0 |
| Standard references | IEC/EN 61643-11; GB/T 18802.11 |
Coordinate the backup protection with the available fault current, selected SPD and circuit design. The published 63 A gG value is a maximum backup-fuse specification, not a requirement to fit that fuse in every installation. Install the IP20 device inside a suitable enclosure; outdoor panels need an enclosure selected for their environment.
OMYT40 or OMYT80: what should I compare?
OMYT40-AC is rated In 20 kA / Imax 40 kA. The OMYT80-AC compact Type 2 series is rated 40/80 kA. Both use the 8/20 μs waveform, but a higher discharge rating alone does not determine the correct selection. Compare the voltage-specific Up, backup protection, connection arrangement and dimensions against the panel design.
Gunakan OOHMAGE AC and DC SPD range to compare other types and current classes. The SPD type and rating selection guide explains the Type 1, Type 1+2 and Type 2 distinctions.
Prepare a panel-specific quotation
Send OMYT40-AC, the Uc version, 2P / 1P+NPE / 4P / 3P+NPE arrangement and quantity through Request Quote. Add the AC system voltage, earthing arrangement, remote-contact requirement, destination and required delivery date. If the model is not yet fixed, send the panel specification or drawing.
Request the matching datasheet, outline drawing and wiring diagram, together with any model-specific test or certification documents required for your market. Confirm packaging, labeling, warranty terms and shipment details with the quotation. These details help align a batch order with the panel build and procurement schedule.
Common selection questions
Where is OMYT40-AC installed?
It is a DIN-rail device for installation inside a distribution panel or suitable enclosure as part of a coordinated surge-protection design. Its IP20 rating does not provide outdoor weather protection.
Does a 40 kA rating mean this is a Type 1 SPD?
No. Imax 40 kA is an 8/20 μs maximum discharge-current rating for this Type 2 series. It is not a declared 10/350 μs Type 1 impulse-current rating. Use a model with the required test class when the installation specification calls for Type 1 protection.
Can I use this AC model on the DC side of a PV system?
Choose a dedicated DC/PV SPD for the DC circuit. The Uc options on this page are AC ratings. For a DC alternative, review the OMDN40-DC Type 2 SPD against the maximum PV system voltage, connection arrangement and protection design.
What is the difference between a local indicator and remote signaling?
The green/red indicator supports checks at the panel. The optional remote contact provides a status signal to a monitoring system. Specify the remote-contact option and check its load rating and connection diagram before wiring.