OMYN60-AC Type 2 surge protection for distribution panels
OMYN60-AC is a pluggable Type 2 AC surge protective device for low-voltage distribution boards. Its nominal discharge current In is 30 kA and maximum discharge current Imax is 60 kA, both specified with the 8/20 μs waveform. Four Uc versions and six connection arrangements support panel selection for residential, commercial and industrial installations.
The MOV (metal oxide varistor) protection module includes thermal disconnection and green/red status indication. Optional remote signaling supports monitoring away from the panel. Select the voltage version, protection modes and connection arrangement together with the installation design.
Voltage-specific ratings
| Paramètre | 275 V | 320 V | 385 V | 440 V |
|---|---|---|---|---|
| Maximum continuous operating voltage Uc (Vac) | 275 | 320 | 385 | 440 |
| Voltage protection level Up (kV) | ≤1.8 | ≤2.0 | ≤2.2 | ≤2.4 |
| TOV withstand, 5 s — Ut (Vac) | 335 | 335 | 500 | 580 |
| TOV disconnection, 120 min — Ut (Vac) | 440 | 440 | 650 | 770 |
Uc is the maximum continuous operating voltage; Up is the voltage protection level. Match the selected values to the supply and equipment requirements. TOV voltages describe temporary-overvoltage test conditions and are not continuous operating voltages.
Connection options and panel fit
The series lists 1P, 2P, 1P+NPE, 3P, 4P and 3P+NPE configurations. Provide the number of phases, earthing arrangement and required protection modes when selecting a version. Pole count alone does not describe the complete wiring arrangement.
Request the outline drawing and corresponding wiring diagram to check the available panel space, terminal access and connection layout. Confirm whether the order requires a remote status contact as well as local indication.
Electrical and installation data
| Electrical / mechanical item | Published value |
|---|---|
| SPD classification | Type 2 AC |
| Nominal operating voltage Un | 230 Vac |
| Nominal discharge current In (8/20 μs) | 30 kA |
| Maximum discharge current Imax (8/20 μs) | 60 kA |
| Short-circuit current rating Isccr | 25 kA |
| Maximum backup fuse | 100 A gG |
| Power connection | Screw terminals, 2.5–25 mm² |
| Montage | 35 mm DIN rail |
| Status indication | Green / red |
| Remote signaling | Facultatif |
| Remote contact load | 250 V / 0.5 A AC; 30 V / 3 A DC |
| Remote conductor cross-section | Maximum 1.5 mm² |
| Température de fonctionnement | −40°C to +85°C |
| Ingress protection | IP20 |
| Matériau du boîtier | Thermoplastic, UL94 V-0 |
| Standard references | IEC/EN 61643-11; GB/T 18802.11 |
The 100 A gG figure is a maximum backup-fuse specification. Coordinate the upstream protection and available fault current with the selected SPD and circuit. The IP20 device needs a suitable equipment enclosure; an outdoor distribution panel needs an enclosure selected for its exposure conditions.
Compare related Type 2 AC SPDs
For another 30/60 kA AC option, compare OMDN60-AC Type 2 SPD by dimensions, connection arrangement and voltage-specific protection level. For a compact 40/80 kA alternative, review OMYT80-AC compact SPD. A larger Imax alone does not establish the correct device for a panel.
Parcourir le OOHMAGE AC and DC SPD range or use the SPD type and rating selection guide to compare test classes and selection criteria.
Request a configuration-specific quotation
Send OMYN60-AC, the Uc version, connection configuration and quantity through Request Quote. Add the system voltage, earthing arrangement, installation environment and remote-signaling requirement. A panel specification or drawing is useful if the model has not been selected.
Request the matching datasheet, dimensions, wiring diagram and available model-specific test or certification documents. Confirm destination, packing quantity, carton dimensions, labeling and delivery requirements with the quotation. Packaging depends on the selected configuration and order.
Common selection questions
Is OMYN60-AC a Type 1+2 SPD?
This page covers a Type 2 AC series. The 30/60 kA figures are 8/20 μs discharge ratings, rather than a declared 10/350 μs Type 1 impulse-current rating. Select a declared Type 1 or Type 1+2 model when the protection design requires that test class.
Can I use the AC version on a 1000 V solar DC circuit?
Use a dedicated DC/PV SPD for a solar DC circuit. The 275–440 Vac Uc options on this page are AC ratings and cannot be treated as PV DC voltage ratings.
Does IP20 mean the device is weatherproof?
IP20 does not provide weatherproof protection. Install the device inside a suitable panel or enclosure, and select the complete assembly for the installation environment.
Which status option should I request?
The green/red indicator supports local inspection. Specify optional remote signaling when a monitoring system needs the device status, and check the contact rating and wiring diagram before connection.
Demander un devis
Indiquez-nous vos spécifications, la quantité souhaitée ou le cas d'utilisation, et nous vous proposerons un devis sur mesure.