OMYN60-AC Type 2 SPD

Type 2 AC SPD: In 30 kA / Imax 60 kA (8/20 μs). Uc 275/320/385/440 Vac. Six connection options, pluggable modules, status indication and optional remote signaling.

Partager sur :

OMYN60-AC Type 2 surge protection for distribution panels

OMYN60-AC is a pluggable Type 2 AC surge protective device for low-voltage distribution boards. Its nominal discharge current In is 30 kA and maximum discharge current Imax is 60 kA, both specified with the 8/20 μs waveform. Four Uc versions and six connection arrangements support panel selection for residential, commercial and industrial installations.

The MOV (metal oxide varistor) protection module includes thermal disconnection and green/red status indication. Optional remote signaling supports monitoring away from the panel. Select the voltage version, protection modes and connection arrangement together with the installation design.

Voltage-specific ratings

Paramètre275 V320 V385 V440 V
Maximum continuous operating voltage Uc (Vac)275320385440
Voltage protection level Up (kV)≤1.8≤2.0≤2.2≤2.4
TOV withstand, 5 s — Ut (Vac)335335500580
TOV disconnection, 120 min — Ut (Vac)440440650770

Uc is the maximum continuous operating voltage; Up is the voltage protection level. Match the selected values to the supply and equipment requirements. TOV voltages describe temporary-overvoltage test conditions and are not continuous operating voltages.

Connection options and panel fit

The series lists 1P, 2P, 1P+NPE, 3P, 4P and 3P+NPE configurations. Provide the number of phases, earthing arrangement and required protection modes when selecting a version. Pole count alone does not describe the complete wiring arrangement.

Request the outline drawing and corresponding wiring diagram to check the available panel space, terminal access and connection layout. Confirm whether the order requires a remote status contact as well as local indication.

Electrical and installation data

Electrical / mechanical itemPublished value
SPD classificationType 2 AC
Nominal operating voltage Un230 Vac
Nominal discharge current In (8/20 μs)30 kA
Maximum discharge current Imax (8/20 μs)60 kA
Short-circuit current rating Isccr25 kA
Maximum backup fuse100 A gG
Power connectionScrew terminals, 2.5–25 mm²
Montage35 mm DIN rail
Status indicationGreen / red
Remote signalingFacultatif
Remote contact load250 V / 0.5 A AC; 30 V / 3 A DC
Remote conductor cross-sectionMaximum 1.5 mm²
Température de fonctionnement−40°C to +85°C
Ingress protectionIP20
Matériau du boîtierThermoplastic, UL94 V-0
Standard referencesIEC/EN 61643-11; GB/T 18802.11

The 100 A gG figure is a maximum backup-fuse specification. Coordinate the upstream protection and available fault current with the selected SPD and circuit. The IP20 device needs a suitable equipment enclosure; an outdoor distribution panel needs an enclosure selected for its exposure conditions.

Compare related Type 2 AC SPDs

For another 30/60 kA AC option, compare OMDN60-AC Type 2 SPD by dimensions, connection arrangement and voltage-specific protection level. For a compact 40/80 kA alternative, review OMYT80-AC compact SPD. A larger Imax alone does not establish the correct device for a panel.

Parcourir le OOHMAGE AC and DC SPD range or use the SPD type and rating selection guide to compare test classes and selection criteria.

Request a configuration-specific quotation

Send OMYN60-AC, the Uc version, connection configuration and quantity through Request Quote. Add the system voltage, earthing arrangement, installation environment and remote-signaling requirement. A panel specification or drawing is useful if the model has not been selected.

Request the matching datasheet, dimensions, wiring diagram and available model-specific test or certification documents. Confirm destination, packing quantity, carton dimensions, labeling and delivery requirements with the quotation. Packaging depends on the selected configuration and order.

Common selection questions

Is OMYN60-AC a Type 1+2 SPD?

This page covers a Type 2 AC series. The 30/60 kA figures are 8/20 μs discharge ratings, rather than a declared 10/350 μs Type 1 impulse-current rating. Select a declared Type 1 or Type 1+2 model when the protection design requires that test class.

Can I use the AC version on a 1000 V solar DC circuit?

Use a dedicated DC/PV SPD for a solar DC circuit. The 275–440 Vac Uc options on this page are AC ratings and cannot be treated as PV DC voltage ratings.

Does IP20 mean the device is weatherproof?

IP20 does not provide weatherproof protection. Install the device inside a suitable panel or enclosure, and select the complete assembly for the installation environment.

Which status option should I request?

The green/red indicator supports local inspection. Specify optional remote signaling when a monitoring system needs the device status, and check the contact rating and wiring diagram before connection.

Demander un devis

Indiquez-nous vos spécifications, la quantité souhaitée ou le cas d'utilisation, et nous vous proposerons un devis sur mesure.

+86-18757092555 Téléphone info@oohmage.com E-mail Discuter sur WhatsApp WhatsApp