OMDN40-AC Type 2 AC Surge Protective Device

OMDN40-AC Type 2 AC surge protection. Uc options: 275 / 320 / 385 / 440Vac.

  • In 20kA; Imax 40kA
  • IP20; 35mm DIN rail
  • Confirm the voltage version, poles and installation conditions
Outdoor installations require a suitable protective enclosure.

Teilen auf:

OMDN40-AC Type 2 AC Surge Protective Device

OMDN40-AC is a Type 2 AC surge protective device series. Compare the Uc voltage versions and the applicable discharge ratings before specifying a device for the project.

Electrical Specifications by Voltage Version

Parameter275 V AC320 V Wechselstrom385 V Wechselstrom440 V AC
SPD typeTyp 2Typ 2Typ 2Typ 2
AC operating voltage Un230 V Wechselstrom230 V Wechselstrom230 V Wechselstrom230 V Wechselstrom
Maximale Dauerbetriebsspannung Uc275 V AC320 V Wechselstrom385 V Wechselstrom440 V AC
Nominal discharge current In (8/20 µs)20 kA20 kA20 kA20 kA
Maximum discharge current Imax (8/20 µs)40 kA40 kA40 kA40 kA
Voltage protection level Up≤1,5 kV≤1,6 kV≤ 1,8 kV≤ 2,0 kV
Short-circuit current rating Isccr25 kA25 kA25 kA25 kA
Maximum backup fuse63A gG fuse63A gG fuse63A gG fuse63A gG fuse

Use the column for the selected voltage version. Confirm the supply system, protection configuration and upstream coordination before ordering.

Installation and Mechanical Data

Main terminal conductorsScrew terminal, 2.5–25mm²
Normal / fault indicationGreen / red
Remote contact maximum load250V / 0.5A AC; 30V / 3A DC
Remote signal conductor cross-sectionMaximum 1.5mm²
Installation35-mm-DIN-Schiene
Betriebstemperatur-40°C to +85°C
SchutzstufeIP20
GehäusematerialThermoplastic material, UL94 V-0
Applicable standard referenceIEC/EN 61643-11; GB/T 18802.11

The device is rated IP20. IP20 does not provide weatherproof protection. For outdoor panels or exposed locations, confirm a suitable protective enclosure and the installation conditions. Coordinate the backup fuse with the selected device and circuit.

Documents and Order Confirmation

Request the applicable datasheet, dimensional drawing, installation instructions and available certification documents for the exact OOHMAGE model. Confirm the document holder, model coverage, destination market, supply scope and packaging with the quotation.

Vor Ihrer Angebotsanfrage

Send the AC system voltage, earthing arrangement, required SPD type, pole configuration, discharge ratings, quantity and installation environment.

Compare the OOHMAGE SPD range or use the quotation form below.

Angebot anfordern

Teilen Sie uns Ihre Anforderungen, die Menge oder den Anwendungsfall mit, und wir unterbreiten Ihnen ein maßgeschneidertes Angebot.

+86-18757092555 Telefon info@oohmage.com E-Mail Auf WhatsApp chatten WhatsApp