OMYCN80-AC Type 2 AC Surge Protective Device

Type 2 AC SPD. In 40 kA / Imax 80 kA (8/20 μs). Uc 275 / 320 / 385 / 440 Vac. IP20, 35 mm DIN rail. Specify voltage, poles and earthing system for a quote.

Teilen auf:

OMYCN80-AC: ratings and application

OMYCN80-AC is a Type 2 AC surge protective device with a nominal discharge current In of 40 kA and a maximum discharge current Imax of 80 kA (8/20 μs). Choose from 275, 320, 385 and 440 Vac Uc versions. The voltage protection level varies with the selected voltage version, as shown below.

Use this series for Type 2 surge protection in AC distribution panels where the selected configuration matches the supply and earthing arrangement. The 40 kA In and 80 kA Imax ratings both use an 8/20 μs waveform. Imax is a maximum discharge-current rating, not a continuous load-current rating. A higher Imax alone does not determine the correct SPD for a panel.

Voltage versions

OMYCN80-AC voltage-dependent ratings
Parameter275 V version320 V version385 V version440 V version
Maximum continuous operating voltage Uc (Vac)275320385440
Voltage protection level Up (kV)≤2.0≤2.2≤2.5≤2.8
TOV withstand, 5 s — Ut (Vac)335335500580
TOV disconnection, 120 min — Ut (Vac)440440650770

Uc is the maximum voltage that may be continuously applied to the SPD. Select it against the actual system voltage and earthing arrangement. TOV test voltages are temporary-overvoltage test conditions, not permissible continuous operating voltages.

Shared electrical and installation data

SPD classificationTyp 2
Nominal AC operating voltage Un230 Vac
Nominal discharge current In (8/20 μs)40 kA
Maximum discharge current Imax (8/20 μs)80 kA
Short-circuit current rating Isccr25 kA
Published maximum backup fuse125 A gG; confirm the exact configuration before selection
Power terminalsScrew terminals, 2.5–25 mm²
Montage35 mm DIN rail
Status indicationGreen / red
Remote contact rating250 V / 0.5 A AC; 30 V / 3 A DC
Remote connection conductorMaximum 1.5 mm²; confirm remote-contact option when ordering
Betriebstemperatur−40°C to +85°C
Ingress protectionIP20

The published backup-fuse value is not a universal installation recommendation. Coordinate upstream protection, the available fault current and the selected SPD arrangement using the model-specific installation information. Install the IP20 device inside a suitable enclosure; it is not a weatherproof outdoor unit.

Choose the correct panel configuration

  1. Specify the supply voltage, number of phases and earthing system.
  2. Select the required SPD type and Uc version; check Up against the equipment and protection design.
  3. Confirm poles, protection modes, upstream protection and remote indication.
  4. Request the exact connection diagram, outline drawing and applicable model documents before finalizing the panel design.

Compare related AC SPDs

For Type 2 alternatives, compare OMYCN80-AC, 40/80 kA, OMYCN100-AC, 50/100 kA und OMYCN120-AC, 60/120 kA. Compare current ratings together with the voltage version, Up and protection configuration.

See the SPD type and rating selection guide for the difference between Type 1, Type 1+2 and Type 2. Browse the AC and DC SPD range to compare applications and series.

Request a configuration-specific quote

Use Request Quote and include OMYCN80-AC, the Uc version, poles, earthing system, quantity and destination. Add the upstream protective device and any remote-signaling requirement so we can confirm a suitable configuration and the documents required for your project.

Common selection questions

Can this AC SPD be used on a solar DC circuit?

Select a dedicated DC SPD for a DC circuit. AC and DC voltage ratings are not interchangeable. This page covers the AC series.

Does the kA rating describe the panel load?

No. The kA figures here describe surge discharge tests. Specify the load circuit and upstream protection separately.

Which documents should I request?

Request the datasheet and wiring drawing for the exact voltage and pole configuration, plus any certificate or test report required for that model and destination market. Confirm the scope of each document before treating it as evidence for the complete series.

Angebot anfordern

Teilen Sie uns Ihre Anforderungen, die Menge oder den Anwendungsfall mit, und wir unterbreiten Ihnen ein maßgeschneidertes Angebot.

+86-18757092555 Telefon info@oohmage.com E-Mail Auf WhatsApp chatten WhatsApp