OMDH6.25-DC Type 1+2 SPD

Type 1+2 DC SPD, 600–1500 Vdc. Compare published voltage-specific current ratings and select the exact SKU. Product image shows a 600 Vdc / 40 kA Imax configuration.

Teilen auf:

Type 1+2 DC SPD: select the exact voltage configuration

OMDH6.25-DC is a Type 1+2 DC surge protective device family for PV and DC protection projects. Select the exact voltage and current configuration rather than using the series name alone as a complete specification.

The electrical table below presents the published 50 kA Imax configurations. The product image illustrates a 600 Vdc / 40 kA Imax configuration, whose nameplate ratings are listed separately. Specify the required configuration in your inquiry so that the quoted SKU, datasheet and product labeling match.

Voltage-dependent selection data

Published OMDH6.25-DC electrical-table configurations — Imax 50 kA
Parameter600 V version800 V version1000 V version1200 V version1500 V version
Maximum continuous operating voltage Ucpv (Vdc)600800100012001500
Voltage protection level Up (kV)≤2.6≤3.2≤3.8≤4.5≤5.2
In (8/20 μs), kA2020202020
Imax (8/20 μs), kA5050505050
Iimp (10/350 μs), kA6.256.256.2553
Itotal (10/350 μs), kA12.512.512.5106

These values follow the published electrical table for the configurations shown. The 1500 Vdc series listing also discloses a 5 kA Iimp configuration; it is separate from the 3 kA Iimp entry in this table. State the required Iimp and complete SKU in the quotation rather than selecting by voltage alone. Confirm the SKU-specific short-circuit rating, connection arrangement and backup protection in the applicable installation documents.

Pictured configuration: 600 Vdc / 40 kA Imax

SPD typeType 1+2 DC
Ucpv600 Vdc
In / Imax (8/20 μs)20 / 40 kA
Iimp (10/350 μs)6.25 kA
Itotal (10/350 μs)12.5 kA
Nach oben≤2.6 kV

Iimp and Itotal describe different ratings. Itotal is the published total discharge-current rating for the multipole assembly; it should not be substituted for the individual Iimp figure. Ratings tested at 10/350 μs are also not interchangeable with the 8/20 μs In and Imax values.

Installation and monitoring

Montage35 mm DIN rail
Power terminalsScrew terminals, 2.5–25 mm²
Status indicationGreen / red
Betriebstemperatur−40°C to +85°C
Ingress protectionIP20
Optional remote contact rating250 V / 0.5 A AC; 30 V / 3 A DC
Remote wiring conductorMaximum 1.5 mm²; confirm remote-contact version when ordering

Install the IP20 device inside a suitable enclosure. The SPD itself is not weatherproof. Confirm the mounting environment, wiring diagram and upstream DC/PV protective device for the exact configuration before installation.

Compare protection options

For a Type 2 DC alternative, compare OMDN40-DC, In 20 kA / Imax 40 kA. For another Type 1+2 family, review OMDH9-DC voltage-specific ratings. Select the type and voltage required by the installation design before comparing surge-current figures.

Read the solar PV surge protection guide, browse the DC SPD range, and review PV combiner box configurations. The main SPD selection page compares AC and DC series.

Specify your PV circuit for quotation

  • Provide the maximum PV open-circuit voltage, including the cold-weather design condition.
  • State the required SPD type, voltage version, protection arrangement and remote-contact option.
  • Include the combiner or inverter application, enclosure conditions, quantity and destination.
  • Request the exact wiring diagram, outline drawing, backup-protection requirements and applicable model documents.

Use Request Quote with these details to obtain a configuration-specific quotation. Do not select a PV SPD using the inverter AC output voltage or the discharge-current rating alone.

PV SPD selection questions

Can an AC SPD replace this DC unit?

No. Specify a device rated for the DC circuit and its maximum operating voltage. AC and DC ratings are not interchangeable.

Does IP20 mean the product can be installed outdoors?

The device needs a suitable protective enclosure. Check the complete enclosure and installation requirements for an outdoor project.

Which certificates apply to my order?

Request the certificate or test report for the exact model, voltage and protection configuration. Check the document holder, model coverage and destination-market requirements before ordering.

Angebot anfordern

Teilen Sie uns Ihre Anforderungen, die Menge oder den Anwendungsfall mit, und wir unterbreiten Ihnen ein maßgeschneidertes Angebot.

+86-18757092555 Telefon info@oohmage.com E-Mail Auf WhatsApp chatten WhatsApp